Skip to main content
Share:

Command Module


The Command Display Module features a user interface which consist of a TFT color display, navigation buttons and status LED’s. Configuration of the Command Display Module (and associated detectors across the SenseNET network ) can be done via the user interface, or via a computer using Remote software. The TFT color display support simple operations like changing configuration options via a menu driven structure, but also advanced features like viewing the chart recording in graphical format.

The Command Display Module support up to 127 modules across the SenetNET network. The 127 modules can be any combination of ModuLaser modules as well as Micra’s and HSSD2’s. The use of the Command Display Module creates an easy to use central point from where all modules/detector on the network can be accessed, and all alarms and faults are reported.
  • Modular Design: Separate centrally-controllable detector modules allow efficient piping and discrete zones with no overlap
  • Zoned aspirating smoke detection: Individual detector modules provide detection for individual areas or zones, specific zone alarm information can be transmitted to the main fire alarm panel via a common APIC address card in the display module or through dedicated alarm relays within each detector module
  • Simplified installation: Ingenious docking station design allows detectors to be easily connected together as a group. Sensitive electronics are easily removed to ensure they will not be damaged during first fix installation. Aspirating pipework and cable entries can easily be made into either the top or the bottom of the unit
  • Intuitive user interface: Bright easy-to-see color TFT display and universal navigation and control buttons take the guesswork out of programming and diagnostics
  • Easy pipe connection: The quick fit pipe adaptor system locks down securely, yet leaves plenty of room for easy pipe connection and removal
  • Quick location of smoke: Each detector module is self-contained, which means no delays in determining in which zone (sampling pipe) smoke is present
General
  • Status indication: LED's
  • User interface: TFT and navigation buttons on Normal and Command Display Modules
  • Alarm levels: 4 (Aux,​ Pre-alarm,​ Alarm and Alarm 2)
  • Event log: 20 000 events per module
  • RS485 support: Yes (SenseNET and SenseNET+)
  • Connectivity: USB (x2),​ IP and APIC on Display Module,​ with Modbus on Command Display Module
Electrical
  • Operating voltage: 18 to 30 VDC
  • Current consumption:
    Display Module (at 24 VDC):
    204 mA - Minimum Display Module
    232 mA - Standard Display Module
    232 mA - Command Display Module
    Detector Module (at 24 VDC):
    260 mA - fan speed 1
    380 mA - fan speed 6 (default speed)
    940 mA - fan speed 16
Detection
  • Detection principle: Laser light scattering mass detection and particle evaluation
  • Particle sensitivity range: 0.003 to 10 microns
Sampling pipe
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Quantity sampling holes:
    Up to 20 - Class A per detector module
    Up to 40 - Class B per detector module
    Up to 50 - Class C per detector module
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Inlet size: 27 or 25 mm (1.06 or 0.98 in) outer diameter
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Inlet location: Top or bottom
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Exhaust size: 27 or 25 mm (1.06 or 0.98 in) outer diameter
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Exhaust location: Top or bottom
Input
  • Input quantity: 2 per module
  • Input type and rating: Supervised
  • Termination: 15 KΩ 5% 1/4 W
  • Programmable: Yes
Output
  • Output quantity: 3 per module
  • Output type and rating: Voltage free (contact rating 2 A at 30 VDC / NO/NC/C)
  • Programmable: Yes
Physical
  • Physical dimensions: W x D x H 110.5 x 133.5 x 300 mm (4.35 x 5.25 x 11.8 in)
  • Net weight:
    Display Module: 1.18 Kg (2.6 lb.)
    Detector Module: 1.57 Kg (3.46 lb.)
  • Colour: Cream
  • Mounting type: Surface mount
  • Cable entries: 2 at the bottom,​ 2 at the rear,​ 2 at the top on Detector Module,​ and 3 at the top on the Display Module
Environmental
  • Operating temperature: 
    Equipment: -20 to +60 °C (-4 to +140 °F)
    Sampled air: -20 to +60 °C (-4 to +140 °F)
  • Relative humidity: 0 to 95% noncondensing
  • Environment: Indoor
  • IP rating: IP40
Standards & regulation
  • Compliancy: REACH,​ RoHS
  • Certification: BOSEC,​ CPR,​ CSIRO,​ EN54-20,​ LPCB
  • BOSEC approved
  • CPR approved
  • CSIRO approved
  • EN54-20 approved
  • LPCB approved
  • Modular Design: Separate centrally-controllable detector modules allow efficient piping and discrete zones with no overlap
  • Zoned aspirating smoke detection: Individual detector modules provide detection for individual areas or zones, specific zone alarm information can be transmitted to the main fire alarm panel via a common APIC address card in the display module or through dedicated alarm relays within each detector module
  • Simplified installation: Ingenious docking station design allows detectors to be easily connected together as a group. Sensitive electronics are easily removed to ensure they will not be damaged during first fix installation. Aspirating pipework and cable entries can easily be made into either the top or the bottom of the unit
  • Intuitive user interface: Bright easy-to-see color TFT display and universal navigation and control buttons take the guesswork out of programming and diagnostics
  • Easy pipe connection: The quick fit pipe adaptor system locks down securely, yet leaves plenty of room for easy pipe connection and removal
  • Quick location of smoke: Each detector module is self-contained, which means no delays in determining in which zone (sampling pipe) smoke is present
General
  • Status indication: LED's
  • User interface: TFT and navigation buttons on Normal and Command Display Modules
  • Alarm levels: 4 (Aux,​ Pre-alarm,​ Alarm and Alarm 2)
  • Event log: 20 000 events per module
  • RS485 support: Yes (SenseNET and SenseNET+)
  • Connectivity: USB (x2),​ IP and APIC on Display Module,​ with Modbus on Command Display Module
Electrical
  • Operating voltage: 18 to 30 VDC
  • Current consumption:
    Display Module (at 24 VDC):
    204 mA - Minimum Display Module
    232 mA - Standard Display Module
    232 mA - Command Display Module
    Detector Module (at 24 VDC):
    260 mA - fan speed 1
    380 mA - fan speed 6 (default speed)
    940 mA - fan speed 16
Detection
  • Detection principle: Laser light scattering mass detection and particle evaluation
  • Particle sensitivity range: 0.003 to 10 microns
Sampling pipe
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Quantity sampling holes:
    Up to 20 - Class A per detector module
    Up to 40 - Class B per detector module
    Up to 50 - Class C per detector module
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Inlet size: 27 or 25 mm (1.06 or 0.98 in) outer diameter
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Inlet location: Top or bottom
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Exhaust size: 27 or 25 mm (1.06 or 0.98 in) outer diameter
  • Length: Up to 250 m (820 ft.) combined per detector module
  • Exhaust location: Top or bottom
Input
  • Input quantity: 2 per module
  • Input type and rating: Supervised
  • Termination: 15 KΩ 5% 1/4 W
  • Programmable: Yes
Output
  • Output quantity: 3 per module
  • Output type and rating: Voltage free (contact rating 2 A at 30 VDC / NO/NC/C)
  • Programmable: Yes
Physical
  • Physical dimensions: W x D x H 110.5 x 133.5 x 300 mm (4.35 x 5.25 x 11.8 in)
  • Net weight:
    Display Module: 1.18 Kg (2.6 lb.)
    Detector Module: 1.57 Kg (3.46 lb.)
  • Colour: Cream
  • Mounting type: Surface mount
  • Cable entries: 2 at the bottom,​ 2 at the rear,​ 2 at the top on Detector Module,​ and 3 at the top on the Display Module
Environmental
  • Operating temperature: 
    Equipment: -20 to +60 °C (-4 to +140 °F)
    Sampled air: -20 to +60 °C (-4 to +140 °F)
  • Relative humidity: 0 to 95% noncondensing
  • Environment: Indoor
  • IP rating: IP40
Standards & regulation
  • Compliancy: REACH,​ RoHS
  • Certification: BOSEC,​ CPR,​ CSIRO,​ EN54-20,​ LPCB
  • BOSEC approved
  • CPR approved
  • CSIRO approved
  • EN54-20 approved
  • LPCB approved