Share:
EXXFIRE TW
Linear heat detection combined with non-pressurised nitrogen fire suppression. A system designed to protect closed server racks, electrical cabinets and machines up to a volume of 9 m3 to 27 m3 (up to 6 interconnected systems possible). Tested extensively by DMT, Dortmund Germany part TüV Nord. Object protection, securing business critical equipment close to the potential source of fire. This level of fire protection will contribute to higher business continuity and prevent fire from spreading in case of a fire incident. Easy installation and no maintenance will contribute to the lowest Total Cost of Ownership (TCO) in the market.
- 10 years shelf life for Cool Gas Generator
- Interconnectivity up to 6 system
- Fire protection for closed cabinets and machines
- Non-Pressurised Nitrogen
- Linear heat detection cable
- Dry Relay Contacts
- Local application
- Easy to Install
- Mounting Kit
- Dimensions:
750: 303 x 443 x 165 mm
1500: 418 x 443 x 165 mm
2250: 580 x 443 x 165 mm - Weight:
750: 10 kg
1500: 18 kg
2250: 25 kg - Extinguishing Agent: Nitrogen N2
- Gas Mass (Volume):
750: 0.9 kg
1500: 1.8 kg
2250: 2.7 kg - Protected Volume:
750: 1.5 m3
1500: 3.0 m3
2250: 4.5 m3 - Design Concentration:
Class A: 40.3 %
Higher hazard Class A: 45.2 %
Class B: 47.6 % - Output Pressure: 3-5
- ADR:
Class Un-used: 9, UN 3268;
Class Used: 9, UN3363 (exempt) - Protection Rating:
Enclosure Class: IP30
Electronic Box: IP55
Generator Class: IP67 - Voltage (Mains): 110/230V AC
- Backup Power: 12 Hours, 4 Years
- Lifetime Generator: 10 years
- Operating Temperature Range: 0 to 54oC
- Generators: 1
- Gas Output Noise Level:
With Silencer: <127dB
Without Silencer: <99dB - Thermal Wire Detection: 68oC to 104oC
- 10 years shelf life for Cool Gas Generator
- Interconnectivity up to 6 system
- Fire protection for closed cabinets and machines
- Non-Pressurised Nitrogen
- Linear heat detection cable
- Dry Relay Contacts
- Local application
- Easy to Install
- Mounting Kit
- Dimensions:
750: 303 x 443 x 165 mm
1500: 418 x 443 x 165 mm
2250: 580 x 443 x 165 mm - Weight:
750: 10 kg
1500: 18 kg
2250: 25 kg - Extinguishing Agent: Nitrogen N2
- Gas Mass (Volume):
750: 0.9 kg
1500: 1.8 kg
2250: 2.7 kg - Protected Volume:
750: 1.5 m3
1500: 3.0 m3
2250: 4.5 m3 - Design Concentration:
Class A: 40.3 %
Higher hazard Class A: 45.2 %
Class B: 47.6 % - Output Pressure: 3-5
- ADR:
Class Un-used: 9, UN 3268;
Class Used: 9, UN3363 (exempt) - Protection Rating:
Enclosure Class: IP30
Electronic Box: IP55
Generator Class: IP67 - Voltage (Mains): 110/230V AC
- Backup Power: 12 Hours, 4 Years
- Lifetime Generator: 10 years
- Operating Temperature Range: 0 to 54oC
- Generators: 1
- Gas Output Noise Level:
With Silencer: <127dB
Without Silencer: <99dB - Thermal Wire Detection: 68oC to 104oC