Skip to main content
Share:

Sigma Local Control Station


The Sigma-SI Status Units are designed in accordance with Australian Standard AS ISO 14520.1-2009 Gaseous fire-extinguishing systems – Physical properties and system design – General requirements (ISO 14520-1:2006, MOD).

The Status Units are designed to extend the indications and some controls of Sigma XT extinguishant control panels to other locations within the fire protection system to make operation of the system more practical within areas that have multiple access points (or doors). A maximum of seven status units may be connected to each control panel extinguishant area. All units connect to a two wire data ECU-LCS communications. Size: 186W x 132H x 55D.
  • Detailed indication of the status of the control panel
  • Manual only and Automatic and Manual mode select key switch option
  • Monitored data connection
  • Robust, high quality enclosure
  • Remote Hold input (monitored)
  • Countdown timer shows time remaining until release
  • Construction: 1.2mm mild sheet steel
  • IP Rating (Standard unit): IP30
  • Colour - lid & box: BS 00 A 05 grey - fine texture
  • Weight: 1kg (all units)
  • Power supply: 21 to 30 V DC
  • Maximum current draw: 0.07A
  • Max. number of status units: 7
  • Quiescent current: 0.033A
  • Cable capacity: 2.5mm2 per terminal
  • Monitored inputs end of line resistor: 6K8 0.5W Resistor
  • Monitored inputs normal threshold: 8K ohm to 1K ohm
  • Monitored inputs trigger threshold: 700 ohms to 100 ohms
  • Monitored inputs: 99 ohms to 0 ohms
  • Short circuit threshold data connection: Two wire RS485 connection (max 1200 metres)
  • Size: 190 x 136 x 60 (mm)
  • Detailed indication of the status of the control panel
  • Manual only and Automatic and Manual mode select key switch option
  • Monitored data connection
  • Robust, high quality enclosure
  • Remote Hold input (monitored)
  • Countdown timer shows time remaining until release
  • Construction: 1.2mm mild sheet steel
  • IP Rating (Standard unit): IP30
  • Colour - lid & box: BS 00 A 05 grey - fine texture
  • Weight: 1kg (all units)
  • Power supply: 21 to 30 V DC
  • Maximum current draw: 0.07A
  • Max. number of status units: 7
  • Quiescent current: 0.033A
  • Cable capacity: 2.5mm2 per terminal
  • Monitored inputs end of line resistor: 6K8 0.5W Resistor
  • Monitored inputs normal threshold: 8K ohm to 1K ohm
  • Monitored inputs trigger threshold: 700 ohms to 100 ohms
  • Monitored inputs: 99 ohms to 0 ohms
  • Short circuit threshold data connection: Two wire RS485 connection (max 1200 metres)
  • Size: 190 x 136 x 60 (mm)